In electrical engineering, a disconnector, disconnect switch or isolator switch is used to ensure that an electrical circuit is completely de-energized for service or maintenance. They are only used for breaking the circuit and are often found in electrical distribution and substation, where machinery must have its source of driving power removed for adjustment or repair. Disconnectors can be manual or motor operated and may be paired with an earthing switch to ground the portion that has been isolated from the system for ensuring the safety of equipment and the personnel working on it.High-voltage isolation switches are used in electrical substations to allow isolation of apparatus such as circuit breakers, transformers, and transmission lines, for maintenance. The disconnector is usually not intended for normal control of the circuit, but only for safety isolation. Unlike load switches and circuit breakers, disconnectors lack a mechanism for suppression of electric arcs, which occurs when conductors carrying high currents are electrically interrupted. Thus, they are off-load devices, with very low breaking capacity, intended to be opened only after the current has been interrupted by some other control device.
Summary
GW1-12(36)/630-20(25) outdoor AC high voltage disconnect switch (disconnect switch for short) is used to open and close circuit with voltage but no-load 50/60Hz, 12(36)kV power system, The anti-pollution type can be used in the serious pollution area. Three pole linkage, good synchronous performance.
Ambient Condition
Altitude: ≤3000m;
Ambient temperature: -30ºC ~+40ºC;
Wind speed: ≤35m/s;
Air pollution: IV;
Earthquake intensity: ≤8 degree;
Ice thickness: ≤10mm.
Model
Structure Feature
This disconnect switch consists of frame, operating insulating, static contactor, blade, linkage spring mechanism, etc.
Frame: 5mm chickness bended armor plate, there are holes on the frame to fixed post insulator.
Post and operating insulator: adopt ZS-12, 36 series outdoor clubbed post insulator, The mini resist bend load is 4000N.
Static contactor: it is made of violet copperplate and fixed on post insulator.
Blade: it is made of rectangular violet copperplate, there is an press-spring to adjust press.
The switch vertical or horizontal installed in outdoor with CS mechanism.
Note: For detail, please refer to the catalogue.
No. |
Item |
Unit |
Data |
1 |
Rated volatge |
kV |
12,36 |
2 |
Rated current |
A |
630 |
3 |
Rated power frequency |
Hz |
50/60 |
4 |
Rated peak withstand current |
kA |
50,63 |
5 |
Rated short-time withstand current |
kA |
20,25 |
6 |
Rated short-time withstand current duration |
S |
4 |
7 |
Main loop resistance |
μΩ |
12kV≤90,36kV≤100 |
8 |
1min(dry) power frequency withstand voltage |
kV |
42/48 ,95/115 |
9 |
1min(wet) power frequency withstand voltage |
kV |
30 ,85 |
10 |
Lightning impulse withstand voltage(peak) |
kV |
75/85 , 185/215 |
11 |
Mechanical life |
Times |
2000 |