Cable Joint Kits (Cold & Heat Shrinkable Cable Accessories)
Heat shrinkable cable accessories
Size of condutor:"0":10-16mm2
"1":20-50mm2
"2":70-120mm2
"3":150-240mm2
"4":300-500mm2
cable cores: from 1C to 5C
Voltage grade:"1";1kV,"11":11kV
"24"24kV,"36":33-36kV
Cable type: Y-cross linked polyethyene
power cable "XLPE";
paper insulation cable "PILC"
usage rang:outdoor termination;
indoor termination; straight through joint
Cold shrinkable cable accessories
Size of condutor:"1":20-50mm2
"2":70-120mm2
"3":150-240mm2
"4":300-500mm2
cable cores: from 1C to 5C
Voltage grade:"1";1kV,"11":11kV
"24";24kV,"36":33-36kV
usage rang: outdoor termination; indoor termination; straight through joint
|
Heat shrinkable cable accessories |
Radiation cross-linked heat shrinkable polymer materials for power cable engineering indoor and outdoor protection, with excellent Proof Tracking Index and anti-pollution performance, in harsh environments to maintain long-term, safe and stable operation. Our heat-shrinkable cable accessories have been tested by the Wuhan High Voltage Research Institute, its performance reached the international advanced level of similar products. During the past 10 years, Millions of products sold throughout the country and Southeast Asia, North America has been safe and reliable operation |
|
|
|
Features
Light weight. Reliable operation. Easy installation, waterproof design.
Under -50 ºC to 50 ºC temperature conditions, the service life is over 20 years
shrinkage ratio: Radial ≥ 50%, Axial≤ 10%.
shrinkage temperature: 120ºC~140ºC.
standards: GB / T12706, DL413, JB / T8144, IEEE Std. 48.IEEE Std. 404.VDE 0278.IEC 60502.ESI 09-13
Electrical stress control
Whether the cable accessories can operate reliably depends on whether the electric field stress at the end of the cable cutout can be properly evacuated. The material used in the heat shrinkage stress control tube has a volume resistivity and a dielectric constant that matches the electric field of the cable at the connection. The operation forms an impedance at the end of the cable shield to act as an electrical stress evacuation to ensure that the heat- Operational reliability and extended service life
Technical Data
property |
Insulation tubing |
stress control tubing |
Conductive tubing |
Sheathing |
shed |
Testing standards |
Hardness(shore A) |
≤90 |
≤85 |
≤90 |
≤95 |
≤90 |
GB/T241-2008 |
Tensile Strength |
≥10.0 |
≥10.0 |
≥10.0 |
≥14.0 |
≥10.0 |
GB/T1040-2006 |
Elongation at break(%) |
≥400 |
≥300 |
≥400 |
≥400 |
≥300 |
GB/T1040-2006 |
Tensile Strength after Aging (130ºC,168 hrs) |
±20 |
±20 |
±20 |
±20 |
±20 |
GB/T714-2008 |
Water Absorption(%) |
<0.1 |
- |
- |
<0.1 |
<0.1 |
GB/T103-2008 |
Volume R esistivity |
≥1014 |
≥109~10 |
≤103 |
≤1013 |
≥1014 |
GB/T141-2006 |
Dielectric Strength(KV/mm) |
≥20 |
- |
- |
≥20 |
≥20 |
GB/T1408-1999 |
Proof Tracking Index |
1A3.5 |
- |
- |
- |
1A 3.5 |
GB/T655-2003 |
Dielectric Constant |
- |
15~30 |
- |
- |
- |
GB/T1409-2006 |
0.6/1KV Heat shrinkable cable accessories
L.V 5-cores heat shrinkable straight through joint kit
L.V 4-cores heat shrinkable termination kit
Use and characteristics
1KV heat shrinkable cable accessories products widely used 0.6 / 1KV cross-linked cable terminal and the middle of the continuous insulation treatment, according to the number of cable core can be divided into 1-core. 2-cores. 3-cores.4-cores. 5-cores and other cables to meet the different cross-section. With small size. Light weight. Reliable operation. Easy installation and so on
Performance and indicators
Pilot projects |
standard requirement |
Electrical performance |
5min Power-Frequency withstand voltage test |
8KV, No flash, no breakdown |
5h Power-Frequency withstand voltage test |
7.2KV, No flash, no breakdown |
Mechanical behavior |
tensile strength |
≥12MPa |
Elongation at break |
≥300% |
1KVL.V thermal cable terminal specifications
Applicable cable cross section |
Applicable cable core number |
NO |
Section(mm2) |
1-core |
2-cores |
3-cores |
4-cores |
5-cores |
1 |
10~16 |
SY-1/1.0 |
SY-1/2.0 |
SY-1/3.0 |
SY-1/4.0 |
SY-1/5.0 |
2 |
25~50 |
SY-1/1.1 |
SY-1/2.1 |
SY-1/3.1 |
SY-1/4.1 |
SY-1/5.1 |
3 |
70~120 |
SY-1/1.2 |
SY-1/2.2 |
SY-1/3.2 |
SY-1/4.2 |
SY-1/5.2 |
4 |
150~240 |
SY-1/1.3 |
SY-1/2.3 |
SY-1/3.3 |
SY-1/4.3 |
SY-1/5.3 |
5 |
300~500 |
SY-1/1.4 |
SY-1/2.4 |
SY-1/3.4 |
SY-1/4.4 |
SY-1/5.4 |
1KVL.V heat shrinkable termination kit
Applicable cable cross section |
Applicable cable core number |
Serial number |
Section(mm2) |
1-core |
2-cores |
3-cores |
4-cores |
5-cores |
1 |
10~16 |
jSY-1/1.0 |
jSY-1/2.0 |
jSY-1/3.0 |
jSY-1/4.0 |
jSY-1/5.0 |
2 |
25~50 |
jSY-1/1.1 |
jSY-1/2.1 |
jSY-1/3.1 |
jSY-1/4.1 |
jSY-1/5.1 |
3 |
70~120 |
jSY-1/1.2 |
jSY-1/2.2 |
jSY-1/3.2 |
jSY-1/4.2 |
jSY-1/5.2 |
4 |
150~240 |
jSY-1/1.3 |
jSY-1/2.3 |
jSY-1/3.3 |
jSY-1/4.3 |
jSY-1/5.3 |
5 |
300~500 |
jSY-1/1.4 |
jSY-1/2.4 |
jSY-1/3.4 |
jSY-1/4.4 |
jSY-1/5.4 |
Note: There are armored cables to use accessories package
1-lug 2-Cable core 3-filling gum 4-seal tubing 5-insulation tubing 6-Outdoor heat shrink tube 7-rainshed 8-stress control tubing 9-semi-conductive layer 10-copper screen 11-Three-hole skirt
12-outer jacket 13-copper braid 14-Cable clamp 15-Triangle pad cone 16-Constant force spring
Tips: Recommended heat shrink attachment with constant force spring fixed ground
Use and characteristics
Heat shrinkable medium voltage products are widely used in 6 ~ 35kv cross-linked cable terminal and the middle of the continuous insulation treatment. With small size. Light weight. Reliable operation. Easy installation and so on. According to user needs can be multi-core cable. Double ground structure or special requirements of the product design
Description of type
S - / .
Size of Conductor:"
"0":10-16mm2
Size of Conductor "1":20-50mm2
"2":70-120mm2
Cable cores "3":150-240mm2
"4":300-500mm2
Voltage Grade:1.10.35KV Cable cores:From
1C to 5C
Cable type:Y-Cross Linked Polyethylene For example:
Power Cable"XLPE"; "WSY-11/3.1":
Z-Paper insulation Cable"PILC" 11KV"XLPE"cable
Heat shrinkable Heat-shrinkable
outdoor termination;
Usage rang: W-Outdoor termination; three cores,Size of
N-indoor termination; Conductor is 25-50
J-Straight through joint mm2
Technical Data
NO |
Property |
require |
Typical data |
1 |
Power-Frequency withstand voltage test |
39KV,5min |
No flash, no breakdown |
2 |
Partial discharge test |
15KV,≤10pc |
≤10pc |
3 |
Impulse withstand |
95kv, Positive and negative polarity of 10 times |
No flash, no breakdown |
4 |
Constant pressure load cycle voltage test(in the air) |
22kv, The conductor was heated to (95-100) ° C for each cycle of 8 h, where 5 h was heated for 3 h for a total of 60 cycles |
Assessed by subsequent tests |
5 |
High temperature partial discharge test |
15kv, ≤10pc |
≤10pc |
6 |
Ac withstand |
22kv,15min |
No flash, no breakdown |
7 |
Outdoor terminal salt spray test |
11kv,1000min |
No flash, no breakdown |
8 |
Indoor terminal wet test |
11kv,300min |
No flash, no breakdown |
10KV XPLE heat ahrinkable cable accessories
Applicable cable cross section |
Outdoor termination kit |
Indoor termination kit |
Straight throught joint kit |
NO |
Size of conductor(mm2) |
1-core |
3-cores |
1-core |
3-cores |
1-core |
3-cores |
1 |
25~50 |
WSY-10/1.1 |
WSY-10/3.1 |
NSY-10/1.1 |
NSY-10/3.1 |
JSY-10/1.1 |
JSY-10/3.1 |
2 |
70~120 |
WSY-10/1.2 |
WSY-10/3.2 |
NSY-10/1.2 |
NSY-10/3.2 |
JSY-10/1.2 |
JSY-10/3.2 |
3 |
150~240 |
WSY-10/1.3 |
WSY-10/3.3 |
NSY-10/1.3 |
NSY-10/3.3 |
JSY-10/1.3 |
JSY-10/3.3 |
4 |
300~400 |
WSY-10/1.4 |
WSY-10/3.4 |
NSY-10/1.4 |
NSY-10/3.4 |
JSY-10/1.4 |
JSY-10/3.4 |
5 |
500~630 |
WSY-10/1.5 |
WSY-10/3.5 |
NSY-10/1.5 |
NSY-10/3.5 |
JSY-10/1.5 |
JSY-10/3.5 |
Note: According to customer demand can choose double ground structure
20KV HEAT SHRINKABLE CABLE ACCESSORIES
Use and characteristics
This product is suitable for the voltage level of 12 / 20KV. 18 / 20KV, the nominal cross-section of 25 ~ 400mm2 cross-linked polyethylene insulation, ethylene-propylene rubber insulated single-core, three-core power cable indoor, outdoor terminals and intermediate joints, from the insulation, sealing, connection.
The electrical stress control of this product is parametric type, the use of stress tube. Products from the insulation tube, the semi-conductor tube, stress pipe, casing, branch sets, such as rainshed
10KV /20kv heat ahrinkable cable accessories
Applicable cable cross section |
Outdoor termination kit |
Indoor termination kit |
Straight throught joint kit |
NO |
Size of conductor(mm2) |
1-core |
3-cores |
1-core |
3-cores |
1-core |
3-cores |
1 |
25~50 |
WSY-20/1.1-12 |
WSY-20/3.1-12 |
NSY-20/1.1-12 |
NSY-20/3.1-12 |
JSY-20/1.1-12 |
JSY-20/3.1-12 |
2 |
70~120 |
WSY-20/1.2-12 |
WSY-20/3.2-12 |
NSY-20/1.2-12 |
NSY-20/3.2-12 |
JSY-20/1.2-12 |
JSY-20/3.2-12 |
3 |
150~240 |
WSY-20/1.3-12 |
WSY-20/3.3-12 |
NSY-20/1.3-12 |
NSY-20/3.3-12 |
JSY-20/1.3-12 |
JSY-20/3.3-12 |
4 |
300~400 |
WSY-20/1.4-12 |
WSY-20/3.4-12 |
NSY-20/1.4-12 |
NSY-20/3.4-12 |
JSY-20/1.4-12 |
JSY-20/3.4-12 |
Note: According to customer demand can choose double ground structure
18KV /20kv heat ahrinkable cable accessories
Applicable cable cross section |
Outdoor termination kit |
Indoor termination kit |
Straight throught joint kit |
NO |
Size of conductor(mm2) |
1-core |
3-cores |
1-core |
3-cores |
1-core |
3-cores |
1 |
25~50 |
WSY-20/1.1-18 |
WSY-20/3.1-18 |
NSY-20/1.1-18 |
NSY-20/3.1-18 |
JSY-20/1.1-18 |
JSY-20/3.1-18 |
2 |
70~120 |
WSY-20/1.2-18 |
WSY-20/3.2-18 |
NSY-20/1.2-18 |
NSY-20/3.2-18 |
JSY-20/1.2-18 |
JSY-20/3.2-18 |
3 |
150~240 |
WSY-20/1.3-18 |
WSY-20/3.3-18 |
NSY-20/1.3-18 |
NSY-20/3.3-18 |
JSY-20/1.3-18 |
JSY-20/3.3-18 |
4 |
300~400 |
WSY-20/1.4-18 |
WSY-20/3.4-18 |
NSY-20/1.4-18 |
NSY-20/3.4-18 |
JSY-20/1.4-18 |
JSY-20/3.4-18 |
Note: According to customer demand can choose double ground structure
35KV HEAT SHRINKABLE CABLE ACCESSORIES
Use and characteristics
Heat-shrinkable cable accessories are widely used in 35kv AC cable termination and intermediate connections for continuous insulation treatment. This series of products for 35kv grade different forms of cable.
With a small size, light weight, reliable operation, easy installation and so on. According to user needs can be multi-core cable, double ground structure or special requirements of the product design
technical Data
NO |
Property |
require |
Typical data |
1 |
Frequency withstand voltage test |
117KV,5min |
No flash, no breakdown |
2 |
Partial discharge test |
45KV,≤10pc |
≤10pc |
3 |
Impulse withstand |
200kv, Positive and negative polarity of 10 times |
No flash, no breakdown |
4 |
Constant pressure load cycle voltage test(in the air) |
65kv, The conductor was heated to (95-100) ° C for each cycle of 8 h, where 5 h was heated for 3 h for a total of 60 cycles |
Assessed by subsequent tests |
5 |
Ac withstand |
104kv,4h |
No flash, no breakdown |
35kv heat ahrinkable cable accessories
Number of cable cores |
Outdoor termination kit |
Indoor termination kit |
Straight throught joint kit |
Applicable cable cross section(mm2) |
1-core |
WSY-35/1.1 |
NSY-35/1.1 |
JSY-35/1.1 |
50-120 |
WSY-35/1.2 |
NSY-35/1.2 |
JSY-35/1.2 |
150-300 |
WSY-35/1.3 |
NSY-35/1.3 |
JSY-35/1.3 |
400-500 |
3-cores |
WSY-35/3.1 |
NSY-35/3.1 |
JSY-35/3.1 |
50-120 |
WSY-35/3.2 |
NSY-35/3.2 |
JSY-35/3.2 |
150-300 |
WSY-35/3.3 |
NSY-35/3.3 |
JSY-35/3.3 |
400-500 |
Note: According to customer demand can choose double ground structure