| Customization: | Available |
|---|---|
| Type: | Power Source Arrester |
| Application: | Tall Tower |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Type | Rated voltage of arrester KV | Nominal voltage of system (virtual value)KV | Continuous operating voltage (virtual value)KV | Reference voltage not less than D.C (U1mA)KV | Max residual voltage(peak) | 2000μs rectangular impulse current (peak value) A | 4/10μs impulse current (peak value) KA | The max leakage current of 0.75DC refference voltageμA | ||
| YH5W-100/260 | 100 | 110 | 78 | 145 | 291 | 260 | 221 | 400 | 65 | 50 |
| YH5W-102/266 | 102 | 110 | 79.6 | 148 | 297 | 266 | 226 | |||
| YH5W-108/281 | 108 | 110 | 84 | 157 | 315 | 281 | 239 | |||
| YH10W-100/260 | 100 | 110 | 78 | 145 | 291 | 260 | 221 | 600 | 100 | 50 |
| YH10W-102/266 | 102 | 110 | 79.6 | 148 | 297 | 266 | 226 | |||
| YH10W-108/281 | 108 | 110 | 84 | 157 | 315 | 281 | 239 | |||
| YH10W-200/520 | 200 | 220 | 156 | 290 | 582 | 520 | 442 | 600 | 100 | 50 |
| YH10W-204/532 | 204 | 220 | 159 | 296 | 594 | 532 | 452 | |||
| YH10W-216/562 | 216 | 220 | 168.5 | 314 | 630 | 562 | 478 | |||