• High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines
  • High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines
  • High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines
  • High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines

High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines

Breaking Capacity: High
Type: Current Fuse
Usage: High Voltage
Customization:
Shipping Cost:

Estimated freight per unit.

about shipping cost and estimated delivery time.
Payment Method: visa mastercard discover JCB diners club american express T/T
  Initial Payment Full Payment
Currency: US$
Return&refunds: You can apply for a refund up to 30 days after receipt of the products.
From payment to delivery, we protect your trading.
High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines pictures & photos
High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines
US $10-50 / Piece
Min. Order: 1 Piece
Diamond Member Since 2011

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
RDK Type
Shape
Spiral
Fusing Speed
F
Fusing Device
Discoloration
Standard
VDE
Outdoor Installation
Outdoor Expulsion Drop-out Type
Transport Package
Carton
Specification
27kv 100/200a
Trademark
HAIVOL
Origin
China
HS Code
8535100000
Production Capacity
20, 000PCS

Product Description

Introduction

Operational principle

The current transformer built in the cutout sectionalizer can detect the current of the main circuit and send the output to the electronic control for digital handling. When a fault occurs, the upstream recloser (or circuit breaker) opens, the circuit loses voltage and the current is lower than 300mA, the electronic controller can remember this opening time as a "count". As it accumulate the presetting number (1 to 4), the sectionalizer will automatic trips within 180ms of fault interruption to isolate fault. Then the upstream recloser (or circuit breaker) closes to restore power supply to the healthy section of the system to limit outage scope and protect the main feeder in service. If the fault is temporary and is cleared before the sectionalizer counter reaches the presetting number, the sectionalizer remains closed and resets to its original state after its reset time expires.

Counts
The number of counts differentiates real faults from transient faults. When the preset number of countsis registered, the electronic sectionalizer willoperate.
The sectionalizer can be set to 1, 2, 3, 4 counts. It registers a count when a current dead time exceeding200 milliseconds occurs, immediately after a current pick up. This ensures the sectionalizer only registers acount when a recloser has tripped due to a faultcurrent.
The count setting should be one count less than the immediate upstreamrecloser.

Pick upcurrent
The pick up current is the threshold, which must be exceeded in order to register a count. The pick up requires a minimum fault pulse that is 10% greater than the pick up current setting and is longer than 20 milliseconds in duration.

Resetting
Theelectronicsectionalizerwillresetitselfduringthedropoutoperation.Do not need remove the unit from itsmount using a hook stick and reset itmanually.

Service conditions
1.The ambient air temperature is not above 55ºC or below-40ºC.
2.Theaveragevalueoftheambienttemperature,measuredoveraperiodof24h,doesnotexceed 25ºC.
3.The altitude does not exceed 1000 m(3300ft).
4.The wind speed does not exceed 34 m/s (corresponding to 700 Pa on cylindricalsurfaces).
5.The ice coating does not exceed1mm.
6.Thesectionalizershouldnotapplytothoseflammable,explosive,corrosiveandseverevibrationconditions. As to other service conditions not covered in the manual, please contact and consult with the manufacturerfor detailinformation.

Designator and itsmeaning

High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines


Technical data
Rated actuating current: 8 to400A
Reclaim time: 20±5%s
Operation counts:1-4
Sensitivity of pick up current:±10%
Max. load current prior to operation: 0.3A
Min. recloser dead time: 500ms
Min. duration of fault pulse:10ms

High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution LinesHigh Voltage Electric Automatic Sectionalizer Use on Overhead Distribution LinesHigh Voltage Electric Automatic Sectionalizer Use on Overhead Distribution LinesHigh Voltage Electric Automatic Sectionalizer Use on Overhead Distribution LinesHigh Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines
High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

From payment to delivery, we protect your trading.
High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines pictures & photos
High Voltage Electric Automatic Sectionalizer Use on Overhead Distribution Lines
US $10-50 / Piece
Min. Order: 1 Piece
Diamond Member Since 2011

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory & Trading Company
Number of Employees
50
Year of Establishment
2010-05-26